Page 65 - 360.revista de Alta Velocidad - Nº 5
P. 65

Current situation and prospects of electric traction systems used in High-Speed railways






                   This  connection  is  economical  and  easy  to  exploit  and  maintain,  although  there  must  be
                   sufficient connection points to the grid. As can be seen in Figure 9, energy is transmitted from
                   the substation to the train through the catenary and a reinforcing conductor if it existed. The
                   current return is made by the track rails, the return conductor and the ground.























                                             Figure 9. Simple feeding with rail return. (Source: Author).


                          5.2     Autotransformer (AT)

                   The AT system is the configuration adopted when there are not enough connection points to
                   the grid. In this case the distance between collateral substations is usually between 60 and 80
                   kilometers.
                   If a nominal voltage value  is considered in the catenary, this connection is often referred to
                   as the 2 ×  kV system, because as will be seen below, there are actually two electrical circuits
                   in phase opposition. Again, considering the normalized value of electric voltage in catenary,
                   it is called 2 × 25 kV system. This double circuit requires the use of an additional conductor
                   (negative feeder) as well as autotransformers every few kilometers. The main objective is to
                   ensure a voltage drop in adequate catenary considering the greater distance between collateral
                   substations. The operating diagram is shown in Figure 10.
                   Substation transformers can be connected to the same or different electrical phases. In the
                   latter case each transformer will feed to a semi-section of the substation, being necessary to
                   install a neutral zone in the substation. The primary winding of each transformer is connected
                   to the grid and converts the voltage to twice the train operating voltage (50 kV). The secondary
                   of the transformer has two windings and a central connection connected to ground. A secondary
                   winding is connected between the catenary and earth (25 kV). The other secondary winding is
                   connected between the negative feeder and ground (-25 kV).
                   Every 10-15 kilometers, autotransformers are connected between the catenary and the negative
                   feeder with its mid point connected to ground. If a train is located at a point in the section,
                   the autotransformers, which have the property of distributing the current that arrives through
                   the central point in two almost equal parts, force the flow of currents indicated in Figure 10.
                   Considering an ideal hypothesis of operation, the distribution of current consumed by the train
                   is made 100% by the catenary to the pantograph. The currents consumed the train are provided
                   depending on the situation of the train. Thus, in the scheme of Figure 10, 50% of the current
                   flows from the substation to the train through the catenary. The remaining 50% is provided by
                   the autotransformers between which the train is located.


                   International Congress on High-speed Rail: Technologies and Long Term Impacts - Ciudad Real (Spain) - 25th anniversary Madrid-Sevilla corridor  63
   60   61   62   63   64   65   66   67   68   69   70