Page 61 - 360.revista de Alta Velocidad - Nº 5
P. 61

Current situation and prospects of electric traction systems used in High-Speed railways




                       section  is approximately 9 kph with a total time passed since traction of roughly 22 s and
                          2
                   having run roughly 1600 m. Even so, it has been seen that the existence of neutral sections on
                   the line does not affect the total route time and the total amount of electric energy consumed.
                   Even so, and as to be expected, the ideal situation for operation would be to have as few
                   neutral sections as possible.

                          3.4     Active techniques to reduce imbalance. Introduction of Power Electronics

                   Furthermore  power  electronics  applications  can  be  used  to  actively  reduce  the  voltage
                   unbalance  in  the  public  grid.  For  this  purpose  different  technologies  and  applications  are
                   introduced. Furthermore other advantages can be achieved like reduced voltage drop at the
                   TPS. For example static VAR compensators (SVCs) connected to the three-phase grid in parallel
                   to the TPS reduces the voltage unbalance imbalance but require large harmonic filters due to
                   the switching of the thyristors. Then synchronous static converters (STATCOMs) connected to
                   the three-phase or single-phase traction network were used where they also allow to filter the
                   harmonics produced by the traction loads.
                   Static frequency converters have also been used to provide the total power required by the
                   substation, although in a smaller number due to the lower cost of the SVC or STATCOM since
                   these are dimensioned for a fraction of the total power of the substation. These frequency
                   converters  have  evolved  from  back-to-back  converters  to  the  current  modular  multi-level
                   converters (MMC). There are two configurations for MMC converters: AC/AC direct converters
                   that allow to convert power from a three-phase network from 50 Hz to a single-phase network
                   at 16,7 Hz, and the AC/DC/AC indirect converters that allow obtaining from a 50 Hz threephase
                   network a single-phase 50 Hz network.

                   Finally,  in  the  last  years  an  electrification  system  called  Cophase  Power  Supply  has  been
                   developed (the first 5 MW installation was installed in 2015 on the Shanxi Line in China) which
                   is a hybrid solution between a STATCOM and a converter of the total power of the substation.
                   There  are  different  configurations  but  in  all  cases  they  use  a  single-phase  converter  that
                   generates on the three-phase side the current necessary to balance the load and compensate
                   for  the  imbalance  generated  by  a  single-phase  or  three-phase  transformer  from  which  the
                   power is supplied to the single-phase rail network. The converter provides active power to the
                   single-phase network and also allows filtering of the harmonics generated by the loads. As the
                   load to the three-phase grid is balanced, the collateral transformers can be connected to the
                   same phase so it is possible to eliminate the neutral sections.
                   The inclusion of power electronic converters implies the existence of a system of regulation of
                   control its operation, and to a greater or lesser extent, the behaviour of the rail network: from
                   the SVC that hardly influences the voltage of catenary, STATCOM and Cophase Power Supply
                   that can vary the voltage in catenary, and finally, the total power converter that can modify
                   the  voltage  and  frequency.  The  last  two  systems  have  the  possibility  of  operating  without
                   neutral  sections  which  allows them  to distribute  the  load between  collateral  substations,
                   both at active and reactive power levels. These converters may have implemented  control
                   methods to function independently of each other (such as Droop Control which is a method for
                   interconnecting multiple voltage sources for microgrids operating in isolation) or by methods
                   that exchange information, for example, to avoid recirculation by the rail network which is in
                   parallel with the three-phase transport network.




                   2  Data obtained after the tests carried out by ADIF on HSL 050 (Madrid to Barcelona) and HSL 010 (Madrid to Sevilla). An average
                   speed of 270 kph is considered.


                   International Congress on High-speed Rail: Technologies and Long Term Impacts - Ciudad Real (Spain) - 25th anniversary Madrid-Sevilla corridor  59
   56   57   58   59   60   61   62   63   64   65   66