Page 63 - 360.revista de Alta Velocidad - Nº 5
P. 63

Current situation and prospects of electric traction systems used in High-Speed railways




                       The length of the de-energised catenary is also a fundamental parameter for analysing the
                   viability  of installing  this  type  of systems.  Specifically  it  has  been  able  to  conclude  that  if
                   this length is lower than established for an interoperable neutral section (402 m), installing
                   switches will not be viable. The reason lies in considering the circulation in double composition
                   of a 200 m train. In this case if the distance existing between the train’s first wheel and the
                   farthest away pantograph from the second composition the train may carry in service (a small
                   auxiliary distance derived from the coupling of the two trains should also be considered), it is
                   concluded that this distance is the one that determines the maximum length of the deenergised
                   section to be used. Therefore, the greater the no-voltage section the simpler it will be to install
                   a system with these characteristics.

                   5.     AC feeding systems

                   TPS can be considered to be composed of two main subsystems: electric traction substations
                   and the railway distribution line (catenary).
                   The railway distribution line can also be considered composed of the overhead contact line, the
                   return circuit and other equipment that we could call complementary elements. The overhead
                   contact line is formed by several conductors (mainly contact wire, catenary wire and droppers)
                   and their elements of support, cable and insulation (cantilever, tie bar, steady arm, etc.). Its
                   design is characteristic of each technology company or of each infrastructure manager and is
                   specially designed to guarantee the transmission of a certain maximum current to each train
                   (the maximum recommended current in EN 50388 is 680 A for 25 kV 50 Hz) an adequate electrical
                   contact with the pantograph at a certain maximum speed. The return circuit is composed of
                   the rails and other components that they group in the set of complementary elements. These
                   complementary elements depend on each feeding system used.
                   The configurations of the TPS networks are considered from the point of view of the existing
                   type of AC power systems and from the point of view of the unilateral or bilateral connection
                   of the substations. The different types of AC systems of feeding to the High-Speed networks are
                   the following:
                   •  Simple feeding with rail return.

                   •  Autotransformer (AT system).
                   •  Coaxial.
                   The fundamental characteristics that determine the use of each one of them is its capacity to
                   transmit power according to the length of the line and the electromagnetic disturbances that
                   generate to its surroundings.
                          5.1     Simple feeding with rail return or additional return conductor


                   This connection is the configuration adopted when there are sufficient connection points to the
                   transport line. In this case the distance between collateral substations is usually between 35
                   and 40 kilometers. If a nominal voltage value  is considered in the catenary, this connection is
                   often referred to as the 1 ×  kV system. Considering the standard value of electrical voltage
                   in catenary (25 kV), it is called 1 × 25 kV system. The operating diagram is shown in Figure 9.
                   Generally  the  substation  transformers  are  connected  to  the  same  electrical  phases.  In  this
                   way  the  section  of  the  substation  is  connected  to  the  same  electrical  phase,  and  it  is  not
                   necessary to install a neutral zone in the substation. The primary winding of each transformer
                   is connected to the grid and converts this voltage to that of the train (25 kV). The secondary
                   winding is therefore connected between the catenary and earth.




                   International Congress on High-speed Rail: Technologies and Long Term Impacts - Ciudad Real (Spain) - 25th anniversary Madrid-Sevilla corridor  61
   58   59   60   61   62   63   64   65   66   67   68